ATSHIELD S 230M

ATSHIELD S 230M – Protector for single-phase power lines. 2P. Type 1 + 2. Uc = 275 VAC. In = 40 kA. Iimp(10/350) = 30 kA. Up = 1.5 kV. Size 4 DIN.

Tested and certified as a Type 1 + 2 protector according to the UNE-EN IEC 61643-11 standard and the REBT GUIDE-BT-23.

Suitable for equipment of Categories I, II, III, IV according to ITC-BT-23.

Dual terminal connection for easy wiring (limited to 63 A).

Compact multipolar protection.

Consisting of zinc oxide varistors and gas dischargers with the capacity to withstand very high currents.

Coordinated with the protectors of the ATSUB and ATCOVER series.
Short response time.
They do not produce deflagration.
They do not at any time cause the interruption of the supply lines.
Great energy bypass capacity.
Limits consecutive mains currents.

Potential-free output for remote warning.

The protectors of the ATSHIELD series have been tested in official and independent laboratories to obtain their characteristics according to the applicable standards.

TECHNICAL DATA

Reference AT-8618
>>ELECTRICAL
Rated voltage ORn 230 VAC
Maximum operating voltage ORc 275 VAC
Nominal frequency f 50 – 60 Hz
Nominal discharge current per pole 8/20μs In 40 kA
Maximum current per pole (wave 8/20μs) Imax 65 kA
Pole drive current (10/350μs wave) Iimp 30 kA
Specific energy (W/R) 224 kJ/Ω
Ability to turn off subsequent current 50 kAeff
Protection level for wave 8/20μs at In ORp 1500 V
Response time tr 100 ns
Previous fuses 125 A gL/gG
Maximum short circuit current 25 kA
>>DIMENSIONS
Long 72 mm
High 96 mm
Wide 80 mm
Weight 340 gr
Number of DIN modules (DIN 43880) 4
>>ENVIRONMENTAL
Working temperature -40 °C to +70 °C
Status of the protector Interior
Housing protection IP20
>>GENERAL
Protection categories according to REBT I, II, III, IV
Types of tests according to UNE-EN 61643-11 Type 1 + 2
>>CONSTRUCTION
Fixation DIN Rail
Housing material Polyamide
Insulation resistance > 1014
Ω
Self-extinguishing housing Type V-0 according to UNE-EN IEC 60707 (UL94)
Connection type Parallel (one port)
Number of Poles 2
Protector failure message Luminous warning. Green: protector in good condition.
Off: replace.
>>CONNECTION
Minimum multi-row section 4 mm2
Maximum multi-row section 35 mm2
Minimum unifilar section 1 mm2
Maximum unifilar section 35 mm2
Screw thread Philips H2
Tightening torque 3 N·m
>>POTENTIAL FREE CONTACT FOR REMOTE CONTROL
Connection Maximum unifilar / multifilar
section: 1.5 mm
2
Contact output Switched
Operating voltage 250 VAC
Maximum Current 2 A
>>TESTS AND CERTIFICATIONS

Tests certified according to UNE-EN IEC 61643-11.

Meets the requirements of UL 1449.

Application standards: UNE 21186, UNE-EN IEC 62305.

Compliance with EC guidelines.

>>Dimensional Scheme (mm)

null

INSTRUCTIONS

>>INSTALLATION

ATSHIELD protectors are installed in parallel with the low voltage line.

When they are installed as medium protection it is necessary that they are separated from the protections
sufficient and / or thin by a cable of at least 10 meters or, if this is not possible, by an ATLINK type
inductance, in order to achieve the correct coordination between them.

The installation must be carried out without tension on the line and can only be carried out by authorized
professionals.

>>SAFETY and MAINTENANCE

Grounding is a must. For the protection to be correct, the grounding of the entire installation must be joined,
directly or by means of sparks, and their resistance must be less than 10 Ω.

If in its use or installation the indications of this sheet are not respected, the protection ensured by this
equipment may be compromised.