ATCOVER 230T

ATCOVER 230T – 3-phase, neutral and ground protector for three-phase lines of 230V (L-L). Imax(8/20) = 30kA. Up = 700V.

Tested and certified as a Type 2+3 protector according to the UNE-EN IEC 61643-11 standard and the REBT GUIDE-BT-23.

Suitable for equipment of Categories I, II, III, IV according to ITC-BT-23.

Dual terminal connection for easy wiring (limited to 63 A).

Compact multipolar protection.

Protection in common and differential mode.

Coordinated with the protectors of the ATSHOCK, ATSHIELD and ATSUB series.
Short response
time.
They do not produce deflagration.

They do not at any time cause the interruption of the supply
lines.
Great energy bypass capacity.

Limits consecutive mains currents.

Potential-free output for remote warning.

The protectors of the ATCOVER series have been tested in official and independent laboratories to obtain their characteristics according to the applicable standards.

TECHNICAL DATA

Reference AT-8132
>>ELECTRICAL
Rated voltage ORn 230 VAC (L-L)
Rated voltage other lines ORn 130 VAC (L-N,L-GND)
Maximum operating voltage ORc 275 VAC (L-L)
Maximum operating voltage for other lines ORc 145 VAC (L-N,L-GND)
Nominal frequency f 50 – 60 Hz
Nominal discharge current per pole 8/20μs In 10 kA
Maximum current per pole (wave 8/20μs) Imax 30 kA
Protection level for wave 8/20μs at In ORp 700 V
Protection level for wave 1.2/50μs 500 V
Combined wave voltage ORoc 6 kV
Residual voltage with combined wave 6 kV/3 kA 450 V
Response time tr 25 ns
Previous fuses 125 A gL/gG
Maximum short circuit current 25 kA
>>DIMENSIONS
Long 144 mm
High 96 mm
Wide 80 mm
Weight 670 gr
Number of DIN modules (DIN 43880) 8
>>ENVIRONMENTAL
Working temperature -40 °C to +70 °C
Status of the protector Interior
Housing protection IP20
>>GENERAL
Protection categories according to REBT I, II, III, IV
Types of tests according to UNE-EN 61643-11 Type 2+3
Power supply system TT and TNS
>>CONSTRUCTION
Fixation DIN Rail
Housing material Polyamide
Insulation resistance > 1014
Ω
Self-extinguishing housing Type V-0 according to UNE-EN IEC 60707 (UL94)
Connection type Parallel (one port)
Number of Poles 4
Protector failure message Double warning of non-protection by means of a
fault indicator light and a green pilot of good operation.
>>CONNECTION
Minimum multi-row section 4 mm2
Maximum multi-row section 35 mm2
Minimum unifilar section 1 mm2
Maximum unifilar section 35 mm2
Screw thread Philips H2
Tightening torque 3 N·m
>>POTENTIAL FREE CONTACT FOR REMOTE CONTROL
Connection Maximum unifilar /
multifilar section: 1.5 mm
2
Salida contacto Conmutado
Tensión de funcionamiento 250 VAC
Corriente Máxima 2 A
>>TESTS AND CERTIFICATIONS

Ensayos certificados según norma UNE-EN IEC 61643-11.

Cumple con los requisitos de UL 1449.

Normas de aplicación: UNE 21186, UNE-EN IEC 62305.

Conformidad con las directrices CE.

>>Dimensional Scheme (mm)
Esquema dimensional (mm)

INSTRUCTIONS

>>INSTALLATION

ATCOVER protectors are installed in parallel with the low voltage line.

When they are installed in combination with other protectors it is necessary that they are separated by a cable of at least 10 meters or, if this is not possible, by an ATLINK type inductance, in order to achieve the correct coordination between them.

The installation must be carried out without tension on the line and can only be carried out by authorized professionals.

>>SAFETY and MAINTENANCE

Grounding is a must. For the protection to be correct, the grounding of the entire installation must be joined, directly or by means of sparks, and their resistance must be less than 10 Ω.

If in its use or installation the indications of this sheet are not respected, the protection ensured by this equipment may be compromised.