Tested and certified as a Type 1 + 2 protector according to the UNE-EN IEC 61643-11 standard and the REBT GUIDE-BT-23.
Suitable for equipment of Categories I, II, III, IV according to ITC-BT-23.
Dual terminal connection for easy wiring (limited to 63 A).
Compact multipolar protection.
Consisting of zinc oxide varistors and gas dischargers with the capacity to withstand very high currents.
Coordinated with the protectors of the ATSUB and ATCOVER series.
Short response time.
They do not produce deflagration.
They do not at any time cause the interruption of the supply lines.
Great energy bypass capacity.
Limits consecutive mains currents.
Potential-free output for remote warning.
The protectors of the ATSHIELD series have been tested in official and independent laboratories to obtain their characteristics according to the applicable standards.
Reference | AT-8619 |
Rated voltage | ORn | 130 VAC |
Maximum operating voltage | ORc | 150 VAC |
Nominal frequency | f | 50 – 60 Hz |
Nominal discharge current per pole 8/20μs | In | 40 kA |
Maximum current per pole (wave 8/20μs) | Imax | 65 kA |
Pole drive current (10/350μs wave) | Iimp | 30 kA |
Specific energy (W/R) | 224 kJ/Ω | |
Ability to turn off subsequent current | 50 kAeff | |
Protection level for wave 8/20μs at In | ORp | 1500 V |
Response time | tr | 100 ns |
Previous fuses | 125 A gL/gG | |
Maximum short circuit current | 25 kA |
Largo | 72 mm |
High | 96 mm |
Wide | 80 mm |
Weight | 340 gr |
Number of DIN modules (DIN 43880) | 4 |
Working temperature | -40 °C to +70 °C |
Status of the protector | Interior |
Housing protection | IP20 |
Protection categories according to REBT | I, II, III, IV |
Types of tests according to UNE-EN 61643-11 | Type 1 + 2 |
Fixation | DIN Rail |
Housing material | Polyamide |
Insulation resistance |
> 1014 Ω |
Self-extinguishing housing | Type V-0 according to UNE-EN IEC 60707 (UL94) |
Connection type | Parallel (one port) |
Number of Poles | 2 |
Protector failure message | Luminous warning. Green: protector in good condition. Off: replace. |
Minimum multi-row section | 4 mm2 |
Maximum multi-row section | 35 mm2 |
Minimum unifilar section | 1 mm2 |
Maximum unifilar section | 35 mm2 |
Screw thread | Philips H2 |
Tightening torque | 3 N·m |
Connection |
Maximum unifilar / multifilar section: 1.5 mm2 |
Contact output | Switched |
Operating voltage | 250 VAC |
Maximum Current | 2 A |
Tests certified according to UNE-EN IEC 61643-11.
Meets the requirements of UL 1449.
Application standards: UNE 21186, UNE-EN IEC 62305.
Compliance with EC guidelines.
ATSHIELD protectors are installed in parallel with the low voltage line.
When they are installed as medium protection it is necessary that they are separated from the protections
sufficient and / or thin by a cable of at least 10 meters or, if this is not possible, by an ATLINK type
inductance, in order to achieve the correct coordination between them.
The installation must be carried out without tension on the line and can only be carried out by authorized
professionals.
Grounding is a must. For the protection to be correct, the grounding of the entire installation must be joined,
directly or by means of sparks, and their resistance must be less than 10 Ω.
If in its use or installation the indications of this sheet are not respected, the protection ensured by this
equipment may be compromised.