Tested and certified as a Type 1+2 protector according to the UNE-EN IEC 61643-11 standard and the REBT GUIDE-BT-23.
Suitable for equipment of Categories I, II, III, IV according to ITC-BT-23.
Unpluggable modules that allow their replacement in case of breakdown or failure.
Compact multipolar protection.
Consisting of zinc oxide varistors with the ability to withstand very high currents.
Coordinated with the protectors of the ATSHOCK, ATSHIELD and ATCOVER series.
Short response
time.
They do not produce deflagration.
They do not at any time cause the interruption of the supply
lines.
Thermodynamic control
device.
Potential-free output for remote warning.
The protectors of the ATSUB series have been tested in official and independent laboratories to obtain their characteristics according to the applicable standards.
Reference | AT-8049 |
Rated voltage | ORn | 300 VAC |
Maximum operating voltage | ORc | 320 VAC |
Nominal frequency | f | 50 – 60 Hz |
Nominal discharge current per pole 8/20μs | In | 30 kA |
Maximum current per pole (wave 8/20μs) | Imax | 65 kA |
Pole drive current (10/350μs wave) | Iimp | 15 kA |
Protection level for wave 8/20μs at In | ORp | 1800 V |
Protection level for wave 1.2/50μs | 1100 V | |
Protection level 5kA; 8/20μs wave | 1300 V | |
Response time | tr | 25 ns |
Previous fuses | 125 A gL/gG | |
Maximum short circuit current | 25 kA |
Long | 36 mm |
High | 96 mm |
Wide | 80 mm |
Weight | 300 gr |
Number of DIN modules (DIN 43880) | 2 |
Working temperature | -40 °C to +70 °C |
Status of the protector | Interior |
Housing protection | IP20 |
Protection categories according to REBT | II, III, IV |
Types of tests according to UNE-EN 61643-11 | Type 1+2 |
Power supply system | TT |
Fixation | DIN Rail |
Housing material | Polyamide |
Insulation resistance |
> 1014 Ω |
Self-extinguishing housing | Type V-0 according to UNE-EN IEC 60707 (UL94) |
Connection type | Parallel (one port) |
Number of Poles | 2 |
Protector failure message | Mechanical warning. Yellow: protector in good condition. Black: replace. |
Minimum multi-row section | 4 mm2 |
Maximum multi-row section | 35 mm2 |
Minimum unifilar section | 1 mm2 |
Maximum unifilar section | 35 mm2 |
Rosca de tornillo | Philips H2 |
Par de apriete | 3 N·m |
Conexión |
Sección máxima unifilar / multifilar: 1,5 mm2 |
Salida contacto | Conmutado |
Tensión de funcionamiento | 250 VAC |
Corriente Máxima | 2 A |
Ensayos certificados según norma UNE-EN IEC 61643-11.
Cumple con los requisitos de UL 1449.
Normas de aplicación: UNE 21186, UNE-EN IEC 62305.
Conformidad con las directrices CE.
ATSUB protectors are installed in parallel with the low voltage line.
When they are installed as medium protection it is necessary that they are separated from the protections sufficient and / or thin by a cable of at least 10 meters or, if this is not possible, by an ATLINK type inductance, in order to achieve the correct coordination between them.
The installation must be carried out without tension on the line and can only be carried out by authorized professionals.
Grounding is a must. For the protection to be correct, the grounding of the entire installation must be joined, directly or by means of sparks, and their resistance must be less than 10 Ω.
If in its use or installation the indications of this sheet are not respected, the protection ensured by this equipment may be compromised.