ATSUB-4P 40-300 TT

ATSUB-4P 40-300 TT – Protector for TT type power supply lines. With plug-in modules. Connection for remote warning. 4 poles. Type 2. Uc = 555 VAC (L-L). Imax =40 kA. Up(In) = 1500 V. Up(1.2/50) = 900 V. Size 4DIN.

Tested and certified as a Type 2 protector according to the UNE-EN IEC 61643-11 standard and the REBT GUIDE-BT-23.

Suitable for equipment of Categories I, II, III, IV according to ITC-BT-23.

Unpluggable modules that allow their replacement in case of breakdown or failure.

Compact multipolar protection.

Consisting of zinc oxide varistors with the ability to withstand very high currents.

Coordinated with the protectors of the ATSHOCK, ATSHIELD and ATCOVER series.
Short response
time.
They do not produce deflagration.

They do not at any time cause the interruption of the supply
lines.
Thermodynamic control
device.

Potential-free output for remote warning.

The protectors of the ATSUB series have been tested in official and independent laboratories to obtain their characteristics according to the applicable standards.


TECHNICAL DATA

Reference AT-8207
>>ELECTRICAL
Rated voltage ORn 520 VAC (L-L)
Rated voltage other lines ORn 300 VAC (L-N,L-GND)
Maximum operating voltage ORc 555 VAC (L-L)
Maximum operating voltage for other lines ORc 320 VAC (L-N,L-GND)
Nominal frequency f 50 – 60 Hz
Nominal discharge current per pole 8/20μs In 20 kA
Maximum current per pole (wave 8/20μs) Imax 40 kA
Protection level for wave 8/20μs at In ORp 1500 V
Protection level for wave 1.2/50μs 900 V
Protection level 5kA; 8/20μs wave 1200 V
Response time tr 25 ns
Previous fuses 125 A gL/gG
Maximum short circuit current 25 kA
>>DIMENSIONS
Long 72 mm
High 96 mm
Wide 80 mm
Weight 550 gr
Number of DIN modules (DIN 43880) 4
>>ENVIRONMENTAL
Working temperature -40 °C to +70 °C
Status of the protector Interior
Housing protection IP20
>>GENERAL
Protection categories according to REBT I, II, III, IV
Types of tests according to UNE-EN 61643-11 Type 2
Power supply system TT
>>CONSTRUCTION
Fixation DIN Rail
Housing material Polyamide
Insulation resistance > 1014
Ω
Self-extinguishing housing Type V-0 according to UNE-EN IEC 60707 (UL94)
Connection type Parallel (one port)
Number of Poles 4
Protector failure message Mechanical warning. Yellow: protector in good
condition. Black: replace.
>>CONNECTION
Minimum multi-row section 4 mm2
Maximum multi-row section 35 mm2
Minimum unifilar section 1 mm2
Maximum unifilar section 35 mm2
Screw thread Philips H2
Tightening torque 3 N·m
>>POTENTIAL FREE CONTACT FOR REMOTE CONTROL
Connection Maximum unifilar / multifilar
section: 1.5 mm
2
Contact output Switched
Operating voltage 250 VAC
Maximum Current 2 A
>>TESTS AND CERTIFICATIONS

Tests certified according to UNE-EN IEC 61643-11.

Meets the requirements of UL 1449.

Application standards: UNE 21186, UNE-EN IEC 62305.

Compliance with EC guidelines.

>>Dimensional Scheme (mm)

null

INSTRUCTIONS

>>INSTALLATION

ATSUB protectors are installed in parallel with the low voltage line.

When they are installed as medium protection it is necessary that they are separated from the protections
sufficient and / or thin by a cable of at least 10 meters or, if this is not possible, by an ATLINK type
inductance, in order to achieve the correct coordination between them.

The installation must be carried out without tension on the line and can only be carried out by authorized
professionals.

>>SAFETY and MAINTENANCE

Grounding is a must. For the protection to be correct, the grounding of the entire installation must be joined,
directly or by means of sparks, and their resistance must be less than 10 Ω.

If in its use or installation the indications of this sheet are not respected, the protection ensured by this
equipment may be compromised.